Operation
Voltage Monitor Relays provide protection to equipment where an over or under voltage condition is potentially damaging. They monitor either AC single phase (50-400Hz) or DC voltages. No supply (input) voltage is required.The pick-up voltage setting is user-adjustable from 85-115% of the nominal voltage rating. As standard, the drop-out voltage setting is fixed at 3% below the pick-up voltage setting. The relay is energized when the monitored voltage is above the pick-up setting. The relay de-energizes when the monitored voltage is below the drop-out setting.
|
| AC OPERATED |
| NTE Type No. |
Nom. Volt. |
Contact Arr. |
Pick-Up Voltage Range |
Drop-Out Voltage Range * |
Max. Contact Cur, @ 30VDC or 240VAC |
| R67-11A10-24 |
24VAC |
DPDT |
21-27V |
20-26V |
10A |
| R67-11A10-120 |
120VAC |
DPDT |
102-138V |
99-135V |
10A |
| DC OPERATED |
| NTE Type No. |
Nom. Volt. |
Contact Arr. |
Pick-Up Voltage Range |
Drop-Out Voltage Range * |
Max. Contact Cur, @ 30VDC or 240VAC |
| R67-11D10-24 |
24VDC |
DPDT |
21-27V |
20-26V |
10A |
* Fixed at 3% below the pick-up setting.
| ACCESSORIES |
| Mounting Styles |
Description |
NTE Type No. |
| Surface Mount |
8-Pin Octal |
R95-101 |
| Panel Mount |
8-Pin Octal |
R95-118 |
| DIN Rail Mount |
8-Pin Octal |
R95-113 |
|
|
Dimensional Drawing

DPDT, 2 Form "C"

Electrical Specifications
Contact
Rating: 10 Amps resistive at 240VAC, 1/2 HP at 240VAC, 10 Amps resistive at 30VDC
Life: 500,000 operations at full load
Mechanical Life: 7,000,000 operations at no load
Operational Characteristics
Voltage Settings:
Pick-Up: Adjustable from 85-115% of nom.
Drop-Out: Fixed at 3% below pick-up setting
Setting Accuracy: +0%, -5% min; +5%, -0% max
Timing Values:
Operate Time: 50mS
Release Time: 50mS
Power Required: 3VA
Protection
Transient: 10,000V for 20µs
Indicator LED: Red LED on when relay is energized
Reset: Automatic
Environmental Characteristics
Operating: -28°C to +65°C
Note: UL Recognition Pending.
|