| INTERVAL ON - The relay energizes and timing begins when the input voltage is applied. At the end of the time delay period the relay will de-energize. Reset is accomplished by removing, then reapplying the input voltage. |
 |
| DPDT, 2 Form "C" |
 |
| AC or DC OPERATED |
| NTE Type No. |
Nom. Volt. |
Contact Arr. |
Input Cur. Nom. |
Max. Contact Cur, @ 28VDC or 120VAC |
Diag. No. |
| R63-11AD10-12 |
12VAC/DC |
DPDT |
167mA |
10A |
D35 |
| R63-11AD10-24 |
24VAC/DC |
DPDT |
83mA |
10A |
D35 |
| R63-11AD10-120 |
120VAC/DC |
DPDT |
17mA |
10A |
D35 |
| ACCESSORIES |
| Mounting Styles |
Description |
NTE Type No. |
| Surface Mount |
8-Pin Octal |
R95-101 |
| Panel Mount |
8-Pin Octal |
R95-118 |
| DIN Rail Mount |
8-Pin Octal |
R95-113 |
| 8-Pin Octal |
R95-181 |
|
|
| Dimensional Drawing |
Timing Range Chart |
| D35 | |
 |
 |
Electrical Specifications
Contact
Rating: 10 Amps 240VAC or less, 1/3 HP, 240VAC or 120VAC, Pilot Duty 345VA, 120VAC or 240VAC, 50/60Hz
Life: 500,000 operations at full load
Mechanical Life: 7,000,000 operations at no load
Input
Nominal Input Voltages: See Chart
Steady State Input Current: See Chart
Timing
Timing Adjustment Modes Available: See Timing Range Chart
Repeat Accuracy
±0.5% - after established at steady temperature (4 hours)
Timing Tolerance at High End of Range: -0, +10%
Timing Tolerance at Low End of Range: +0, -50%
Reset Time: 60mS Typ
Protection
Transient: Surge Test 10,000V for 20mS
Dielectric Breakdown:
Coil To Contact: 1850 VAC
Across Open Contact: 1850 VAC
Environmental Characteristics
Operating: -20°C to +55°C
Weight
Std: 4.5 ozs. (130 grams) - approx |