| DELAY ON RELEASE - Input voltage must be applied continuously to operate the internal relay. When the control switch is closed, the relay energizes. When the control switch is opened, timing begins. When timing is complete, the relay will de-energize. Time may be reset to zero during timing by closing the control switch. |
 |
| DPDT, 2 Form "C" |
 |
| AC or DC OPERATED |
| NTE Type No. |
Nom. Volt. |
Contact Arr. |
Input Cur. Nom. |
Max. Contact Cur, @ 28VDC or 120VAC |
Diag. No. |
| R61-11AD10-12 |
12VAC/DC |
DPDT |
167mA |
10A |
D36 |
| R61-11AD10-24 |
24VAC/DC |
DPDT |
83mA |
10A |
D36 |
| R61-11AD10-120 |
120VAC/DC |
DPDT |
17mA |
10A |
D36 |
| ACCESSORIES |
| Mounting Styles |
Description |
NTE Type No. |
| Surface Mount |
11-Pin Octal |
R95-104 |
| Panel Mount |
11-Pin Octal |
R95-119 |
| DIN Rail Mount |
11-Pin Octal |
R95-114 |
| 11-Pin Octal |
R95-182 |
|
|
| Dimensional Drawing |
Timing Range Chart |
| D36 | |
 |
 |
Electrical Specifications
Contact
Rating: 10 Amps 240VAC or less, 1/3 HP, 240VAC or 120VAC, Pilot Duty 345VA, 120VAC or 240VAC, 50/60Hz
Life: 500,000 operations at full load
Mechanical Life: 7,000,000 operations at no load
Input
Nominal Input Voltages: See Chart
Steady State Input Current: See Chart
Timing
Timing Adjustment Modes Available: See Timing Range Chart
Repeat Accuracy
±0.5% - after established at steady temperature (4 hours)
Timing Tolerance at High End of Range: -0, +10%
Timing Tolerance at Low End of Range: +0, -50%
Reset Time: 60mS Typ
Protection
Transient: Surge Test 10,000V for 20mS
Dielectric Breakdown:
Coil To Contact: 1850 VAC
Across Open Contact: 1850 VAC
Environmental Characteristics
Operating: -20°C to +55°C
Weight
Std: 4.5 ozs. (130 grams) - approx |